    Is an APC SYA16K154RMP with 4 SYPM4KP’s and 4 SYBT5’s still in use?
    What VA/kVA rating is preferred for the unit? Is this an 8kVA with N+1 redundancy or a full 16kVA unit?
    Provide load draw of connected equipment, either in amps or watts of load connecting to this UPS
    Preferred runtime from the 8/16kVA UPS to provide backup for connected equipment
    Number and type of outlets required from this UPS

     

    Response - 

    We are requesting bids for an APC SYA16K164RMP or equivalent. It should be fully populated - full 16kVA with N+1 redundancy.
    This unit is intended to completely replace the current system in the MDF.  The additonal power modules are for existing APC UPS units.
    The number and type of outlets should be equivalent to what the APC SYA16K164RMP has, which are the following - 
    8 NEMA L5-20R, 4 NEMA L14-30R

      This is the current load on the current UPS we have running our equipment.  We would like enough time to shut down equipment properly, so at least 60 minutes.UPS